Machine Model: CSVGN4
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0 < T3 < Mult*TimeStep then T3 = Mult*TimeStep
- If 0 < T4 < Mult*TimeStep then T4 = Mult*TimeStep
- If 0 < T5 < Mult*TimeStep then T5 = Mult*TimeStep
- Rmin: Generator MVA Base should be approximately equal to the difference between Max Mvar and Min Mvar, if not then Generator MVA Base has been changed to a value which is a difference between Max Mvar and Min Mvar.
- CBase: CBase should be approximately equal to the Generator Max Mvar value, if not then CBase has been change to a value which is the Generator Max Mvar value.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters:
| K | Gain, pu |
| T1 | Time constant, sec |
| T2 | Time constant, sec |
| T3 | Time constant, sec |
| T4 | Time constant, sec |
| T5 | Time constant, sec |
| Rmin | Reactor min Mvar |
| Vmax | Vmax, pu |
| Vmin | Vmin, pu |
| CBase | Capacitor Mvar |
| Vov | Override Voltage, pu |